89InRoom Controller - Operating Instructions
U1
loaddefault dx1
6.4.1 Preconfigurations
10 default configurations for different unit cooling systems are stored in the I/O controller.
Command:
Unit type DX GE1 GE2 AGCW CW
1 circuit dx1 ge11 ge21 agcw1 cw
2 circuits dx2 ge12 ge22 agcw2 cw2
The table contains the parameters for the IOC-
command.
DX1 DX2 CW CW2 AG/CW1 AG/CW2 GE1-1 GE1-2 GE2-1 GE2-2
Compressor 1 configured 1 1 1 1 1 1 1 1
Compressor 2 configured 1 1 1 1
Sensor 5 configured 1 1 1 1 1 1
Sensor 6 configured 1 1 1 1
Sensor 7 configured 1 1 1 1
Sensor 8 configured 1 1
Pump 1 configured 1 1
Pump 2 configured 1 1
Deshum. configured 1 1 1 1 1 1 1 1
GE/CW valve configured 1 1 1 1 1 1
G valve configured 1 1
Dehumidification reduction
20% 20% 20% 20% 20% 20% 20% 20%
Input D GE/CW valve
3
Cooling priority
1 1
The following table displays the differences in relation to the default settings when a pre-configuration is selec-
ted.