5InRoom Controller - Operating Instructions
The InRoom Controller offers maximum possible ope-
rating safety for industrial applications and a versatile
operator interface. There are two interfaces with one
controller.
The InRoom Controller works by having each cooling
unit possess its own controller while all controllers can
be linked together in a bus system.
This way a natural redundancy is obtained that causes
the system to function with the least expense.
The second interface can be accessed using a com
-
puter. Using the screen of a Laptop or PC provides the
best way of visualizing parameter settings. This is the
most comfortable way of doing a component-related
configuration.
Beyond the basic air conditioning functions, the control
system provides some interesting features like an intel-
ligent management of high/low pressure-alarms, a pro-
portional fan speed control which opens a wide spectrum
of applications and time-based functions like:
- week timer
- unit sequencing within definable unit groups
The heart of the control system is the I/O controller on
which up to 4 EAIO/EDIO boards for additional in- and
outputs can be installed. The exploitation of the third
dimension provides maximum accessibility and an easy
board exchange in case of modifications.
The control systems manages four busses:
1. IIC-bus for the communication between the I/O
controller and the EAIO/EDIO boards.
2. RS485 IO-bus for the communication among the
cooling units.
3. RS485 BMS-bus for the communication with a
building management system.
4. RS485 Aux-bus for the communication with optio
-
nal components capable of bus connection.
For service purposes like software download and control
by a remote computer a RS232 interface is located on
the I/O controller in the same way as on the InRoom
Controller interface.
Analogous (A) and digital (D) in- and outputs
A-IN A-OUT D-IN D-OUT
IOC-board 5 4 11 7
EAIO-board 4 4 / /
EDIO-board / / 8 6
Max i mum e q u i pment
IOC + 4 EAIO 21 20 11 7
IOC + 4 EDIO 5 4 43 31
Interfaces
IOC-board
2 x RS485 IO-bus, terminals
4 x IIC-Bus, DB-15
EBUS conn. DB-15
RS232, DB-9
EAIO-board IIC-Bus, DB-15
EDIO-board IIC-Bus, DB-15
EBUS-board
I/O board conn. DB-15
RS485 BMS-bus, terminals
RS485 Aux.-bus, terminals
Operator inter
-
face board
2 x RS485 IO-bus + BMS,
terminals
2 x RS232 BMS + service,
DB-9
1. Presentation of the system