InRoom Controller - Operating Instructions42
T/°C
A6
Control
The corresponding commands:
Times are entered in seconds.
The numbered callouts refer to the corres-
ponding passages in the descriptive text.
Display Cooling
Drycooler
The start temperature for the drycooler is
entered as an absolute value for the water
temperature.
Two different start temperatures for sum
-
mer and winter operation + hysteresis can
be entered.
,,
Note:
The summer/winter operation depends
on the setting in the menu Service/Ge
-
neral settings/control/parameters. (see
page 70)
You can determine, whether the drycooler
alarm shall generate a common alarm
(0= no, 1 = yes).
The drycooler alarm delay can be adjus-
ted.
Setting the priority for the drycooler alarm
means assigning the alarm to an alarm
relay with the adjusted number.
The parameters:
- control factor
- control cycle
- max. control correction
- pre-speed
are only necessary for the GEp-control,
which is explained in a separate manual.
Drycooler
ON
OFF
winter
operation
summer
operation
water
temp.
drycool 1 startwin 15.0
drycool 1 startsum 32.0
drycool 1 hys 3.0
drycool 1 commonalarm 1
drycool 1 alarmdelay 3
drycool 1 alarmprio 3
drycool 1 fact 3
drycool 1 concyc 10
drycool 1 maxc 4
drycool 1 prespeed 100
Zobrazit stránku 41