InRoom Controller - Operating Instructions28
Display
Info
For data logger 1 each
- Displays adjustments, number of data and date
of recent and eldest value.
- Displays the 20 recent values as follows.
- Edits 20 values before the last 20 values (value
21 to 40 going from the actual point of time).
- Edits the eldest 20 values (value 1421 to 1440
going from the actual point of time).
- Edits all values of this day as far as stored.
- Edits the values 1 to 13 going from the actual
point of time.
- Deletes all stored values.
The corresponding commands:
Data logger
Use the data logger to save measured
values or average values (zone data)
calculated by the controller and have
these values displayed in the shape of a
graphical curve so as to show their time
course.
Values of two different sensors can be
simultaneously recorded.
You set the lapse of time which will be
displayed. Further parameters (type of
measured value and cycle) can be adjus-
ted in the service menu.
You can choose among 5 different lapses
of time: hour (adjusting this lapse displays
the recent 3 hours), day, week, month
and year.
The time lapse is displayed in a horizontal
direction; a vertical dashed line marks the
actual time.
The range of the measured value within
the limit values (if existant for this type of
value) is displayed vertically.
Two exterior dashed lines mark the limit
values. An interior dotted line marks the
set value, if existant.
The course of the measured value is dis-
played by a continuous line.
log 1
log 1 1
log 1 2
log 1 72
log 1 15.05.2006
log 1 1 13
log 1 clear
Type.............:1 (Unit room temp)
Store cycle......:15 Min
Number of values.:938
Youngest.........:11.08.2004 15:33:00
Eldest...........:01.08.2004 02:18:00
0001. 11.08.2004 15:33:00 Room temperature 22.9°C
0002. 11.08.2004 15:18:00 Room temperature 23.0°C
0003. 11.08.2004 15:03:00 Room temperature 23.1°C