69InRoom Controller - Operating Instructions
R2, R3
14 15 16 17 T/°C
T/°C
20,5
20
68 70 72 74 r.h/%
r.h/%
50
49
21 22 23 24 T/°C
T/°C
18
17,5
38 39 40 41 r.h/%
r.h/%
50,5
50
Service
Display Gen. settings
Control/Parameters
Using the room control with supply air
limitation causes the control to take place
using a T/H sensor in the return air intake
and a second T/H sensor in the supply
air intake. The control takes place in the
same way as room air control, the tem-
perature setpoint is shifted only when the
supply air temperature exceeds the start
temperature
➋. The extent of the setpoint
increase is determined by a factor which
you enter, as a gradient
➌, in the menu.
The relationship, according to which the
setpoint increase happens, is made clear
by the graph on the left side. A steep
gradient drastically corrects the failure
to meet the supply air temperature, but
has the risk that the control circuit starts
to oscillate.
With humidity control the setpoint shift
takes place in the opposite direction. If the
adjusted starting humidity ➍ is exceeded
by the measured supply air humidity, the
setpoint is reduced. You can also enter a
gradient factor
➎ for this. The relationship
is shown in the graph on the right side.
New setpoint = old setpoint + gradient •
(start value - actual value)
The supply air control with room air limita
-
tion is based on the same control principle
as the supply-air limited room air control.
Only here the setpoint shift works in the
opposite direction, because it works on
the basis that the supply air is colder than
the return air.
If the room temperature exceeds the start
temperature entered, the temperature
setpoint is reduced.
If the room humidity drops below the
starting humidity entered, the humidity
setpoint is increased.
The limit values of all four input variables
are monitored for room air control with
supply air limitation and for supply air
control with room air limitation.
- Room air temperature
- Room humidity
- Supply air temperature
- Supply air humidity
Actual value
Supply air sensor
Setpoint
Room air sensor
Temperature
Humidity
Actual value
Supply air sensor
Setpoint
Room air sensor
Example (temperature):
20.5 = 20 + 0.5 • (16 - 15)
Example (humidity):
49 = 50 + 0.5 • (70 - 72)
Actual value
Room air sensor
Setpoint
Supply air sensor
Temperature
Example:
17.5 = 18 + 0.5 • (22 - 23)
Humidity
Actual value
Room air sensor
Setpoint
Supply air sensor
Example:
50.5 = 50 + 0.5 • (40 - 39)
Note:
For corresponding commands, see previous
page.