11InRoom Controller - Operating Instructions
2.2.3 Assignment - EDIO2
The assignment depends on the unit version (DX1, DX2, CW). For more information, see „2.1.2 Assignment - I/O Controller“
on page 7.
Pin Designation DX1 DX2 CW
1 Din 20 Free Ext. alarm 4 Free
2 Din 21 Free Free Free
3 Din 22 Pump failure 3 Pump failure 3 Free
4 Din 23 Pump failure 4 Pump failure 4 Free
5 Din 24 Free Free Free
6 Din 25 Free Free Free
7 Din 26 Free Free Free
8 Din 27 Free Free Free
9 Dout 14 (NO)
Pump 3 Pump 3 Free10 Dout 14 (COM)
11 Dout 14 (NC)
12 Dout 15 (NO)
Pump 4 Pump 4 Free13 Dout 15 (COM)
14 Dout 15 (NC)
15 Dout 16 (NO)
Free Humidifier on/off /ENS Free
16 Dout 16 (COM)
17 Dout 16 (NC)
18 Dout 17 (NO)
Drycooler 3 Drycooler 3 Free
19 Dout 17 (COM)
20 Dout 17 (NC)
21 Dout 18 (NO)
Drycooler 4 Drycooler 4 Free
22 Dout 18 (COM)
23 Dout 18 (NC)
24 Dout 19 (NO)
Free Free Free
25 Dout 19 (COM)
26 Dout 19 (NC)
27 PWM3
Electrical
expansion valve 2
Electrical
expansion valve 2
Free
28 GND
29 PWM4
Free Free Free
30 GND
X10
SUB-D 15 Bus 3 I
2
C (plug) Bus 3 I
2
C (plug) Bus 3 I
2
C (plug)