85InRoom Controller - Operating Instructions
Range electr. reheat 1 electr. reheat 2 electr. reheat. 3 electr. reheat 4
Type
1 - 2 1 1 1 1
Start
0 - 9.9 1.5 K 2 K 2.5 K 3 K
Stop hysteresi
s 0 - 9.9 0.5 K 0.5 K 0.5 K 0.5 K
Gradient
0.5 - 9.9 0.5 K 0.5 K 0.5 K 0.5 K
Component configured
0 - 1 0 0 0 0
Output D 0 - 31 3 4 12 15
Alarm input
D 0 - 43 4 4 4 23
Alarm priority
0 - 31 0 0 0 0
Common alarm
0 - 1 1 1 1 1
Alarm delay
0 - 100 4 s 4 s 4 s 4 s
Runtime
0 - 4294967295 0 h 0 h 0 h 0 h
Range Hot water reh.
Type
1 - 2 1
Start
0 - 9.9 1.5 K
Stop hysteresi
s 0 - 9.9 0.5 K
Gradient
0.5 - 9.9 0.5 K
Component configured
0 - 1 0
Output D 0 - 31 4
Output A 0 - 20 7
Range Hot gas reheat
Start
0 - 9.9 1.0 K
Stop hysteresi
s 0 - 9.9 0.5 K
Component configured
0 - 1 0
Output D 0 - 31 4
Range Humidifier 1 Humidifier 2 Humidifier 3
Type
1 - 2 2 2 2
Start
0 - 20 0 %r.h. 0 %r.h. 0 %r.h.
Stop hysteresi
s 0 - 20 5 %r.h. 5 %r.h. 5 %r.h.
Gradient
0.5 - 20 10 10 10
Component configure
d 0 - 1 0 0 0
Conductivity meter configured 0 - 1 0 0 0
Output D 0 - 31 13 0 0
Output A 0 - 20 3 6 7
Alarm input
D 0 - 43 6 6 6
Alarm priority
0 - 31 0 0 0
Common alarm
0 - 1 1 1 1
Alarm delay
0 - 100 5 s 5 s 5 s
Alarm input
D 5µS 0 - 43 0 0 0
Alarm priority
5µS 0 - 31 0 0 0
Common alarm
5µS 0 - 1 0 0 0
Alarm delay
5µS 0 - 1000 300 s 300 s 300 s
Alarm input
D 20µS 0 - 43 6 6 6
Alarm priority 20µS
0 - 31 0 0 0
Common alarm 20µS
0 - 1 1 1 1
Alarm delay
20µS 0 - 1000 300 s 300 s 300 s
Runtime
0 - 4294967295 0 h 0 h 0 h
Reheats
Humidifiers