17InRoom Controller - Operating Instructions
Now the bus commands in detail:
- The invite command plus bus I.D. adds a bus par-
ticipant.
- The
del command plus bus I.D. excludes the par-
ticipant from the bus and sends the new I/O-bus
configuration to all participants.
- The
iobus command edits the stored I/O-bus confi-
guration.
- The
checkbus command checks every I.D. address
from 00 to 31 for the presence of a bus participant and
updates the stored bus configuration accordingly.
- The
spreadbusconf command distributes the bus
configuration to all participants.
General
The numbering of any digital or analogous in- or output
begins with number 1. Despite this the digital/analogous
in- or output 0 can be assigned to any component. This
will allow the component to stay part of the configuration
even if it does not take part in the control.
A double assignment of in- and outputs is not possible
with the exception of in-/output 0 and the alarm priorities
(relays).
Whenever a parameter is expressed by a logical function,
0 means no, disabled; 1 means yes, enabled.
If at unit start no valid configuration is found, the configu
-
ration for single refrigerant circuit-units DX1 is loaded.
Note that no year below 2000 can be entered.