InRoom Controller - Operating Instructions38
a
b
a
b
A2
Control
The corresponding commands:
Times are entered in seconds.
The numbered callouts refer to the corres-
ponding passages in the descriptive text.
Display Cooling
Compressor (part 2)
The low pressure alarm can be managed
in a way to avoid a premature and unne-
cessary service intervention.
If the LP switch releases, the compressor
is stopped and restarted after the com
-
pressor pause has elapsed. The LP alarm
is inhibited during the winter start delay
(see page 70).
This way the controller tries to bypass
temporary LP alarms.
You can limit the number od compressor
restarts in "RESTARTS"
b within a time
space which you can adjust in the first
line .
If the maximum number of restarts is
reached, the LP alarm is released and
the compressor is definitely switched off.
Using the optional LP-sensor you can ad
-
just a threshold
a which marks the lower
limit for the permissible pressure range.
With a HP sensor (either part of G-valve
or separate option) high pressure alarms
can be equally managed for the same
reasons as LP alarms.
You can limit the number od compressor
restarts in "RESTARTS"
b within a time
space which you can adjust in the fourth
line .
If the threshold a of the HP is excee-
ded the adjusted number of times, the
HP alarm is released and the measure
which you have adjusted in HP mode
is taken.
0: unit off
1: unit continues operation
comp 1 lptime 2
comp 1 lppress 4.6
comp 1 lptries 6
comp 1 hptime 2
comp 1 hppress 21
comp 1 hptries 3
comp 1 hpmode 1