7InRoom Controller - Operating Instructions
Pin Designation DX1 DX2 CW
1 24VAC
Power supply Power supply Power supply
2 GND
3 GND Reserved Reserved Reserved
4 Din 1 Fan failure Fan failure Fan failure
5 Din 2
Compressor failure Compressor failure
1 Pump failure 1
6 Din 3 Low pressure Low pressure 1 Chiller failure
7 Din 4 E-reheat failure 1-3 E-reheat failure 1-3 E-reheat failure 1-3
8 Din 5 Filter alarm Filter alarm Filter alarm
9 Din 6
Humidifier failure/
ENS 20µS
Humidifier failure/
ENS 20µS
Humidifier failure/
ENS 20µS
10 Din 7 Water detection Water detection Water detection
11 Din 8
Ext. alarm 1 Compressor failure 2 Ext. alarm 1
12 Din 9
Ext. alarm 2 Low pressure 2 Ext. alarm 2
13 Din 10 Remote on/off Remote on/off Remote on/off
14 Din 11 Fire stat Fire stat Fire stat
15 Dout 1 (NO)
Enable fan Enable fan Enable fan
16 Dout 1 (COM)
17 Dout 1 (NC)
18 Dout 2 (NO)
Compressor Compressor 1 Pump 219 Dout 2 (COM)
20 Dout 2 (NC)
21 Dout 3 (NO)
E-reheat 1 E-reheat 1 E-reheat 122 Dout 3 (COM)
23 Dout 3 (NC)
24 Dout 4 (NO)
E-reheat 2 / Hot gas
reheat / HWR*
E-reheat 2 / Hot gas
reheat / HWR*
E-reheat 2 or HWR*25 Dout 4 (COM)
26 Dout 4 (NC)
27 Dout 5 (NO)
Dehumidification or
Hotgas-bypass
Dehumidification or
Hotgas-bypass
On/off Humidifier or ENS
28 Dout 5 (COM)
29 Dout 5 (NC)
30 Dout 6 (NO)
Common alarm 1 Common alarm 1 Common alarm 1
31 Dout 6 (COM)
32 Dout 6 (NC)
33 Dout 7 (NO)
Louver
Compressor 2 Louver34 Dout 7 (COM)
35 Dout 7 (NC)
2.1.2 Assignment - I/O controller
The assignment depends on the unit version (DX1, DX2, CW).
DX1 - Single refrigerant circuit. DX2 - Dual refrigerant circuit. CW - Chilled water circuit.
E.g.: PA311D -> DX1, PGCW452U -> DX2, PCW900D -> CW
*HWR - hot water reheat