InRoom CW/DX – Operating Instructions76
10. Maintenance
10.1 Safety instructions
All maintenance work is to be carried out under strict compliance with the country-specifi c accident prevention
regulations, especially the accident prevention regulations for electrical installations, refrigerating machines
and equipment. Non-compliance with the safety instructions can endanger people and the environment.
Maintenance work is only to be carried out on the units by authorized and qualifi ed specialist staff.
Electrical Hazard
Unless otherwise indicated, remove power before attempting to service this unit. Remove power
at the upstream breaker and disconnect the power cords before servicing. Failure to do so could
result in serious injury or death.
The service personnel must verify that all power has been disconnected before servicing the
unit.
Some verifi cations must be effected with the unit in operation (measuring the current, pressures
and temperatures). In such a case the unit must only be switched on at the master switch after all
mechanical connections have been carried out. The unit must be switched off immediately after
the measuring procedure.
The switch on the front panel does not disconnect all power from the unit. There will still
be voltage present on the main contactors. Wait 5 minutes after shutting off power to the
unit before opening the panels. Capacitance on the fan terminals may hold a hazardous
charge. Avoid contact with the electronics housing as it may be hot immediately after
shutting off the unit.
Warning
Risk of injury. The fans may continue to run after the unit is stopped.
Component Maintenance interval
monthly quarterly half-yearly yearly
Refrigerant circuit
Refrigerant charge x
HP/LP switch x
Sight glass x
Compressor x
Expansion valve x
Air circuit
Heat exchanger x
Fan x
Air fi lter x
Water circuit
Tightness x
Condenser x
Other unit components
Electrics x
Mechanics x
10.2 Maintenance intervals