InRoom CW/DX – Operating Instructions64
Description & Causes
Cylinder depleted
Lack of supply water
Excessive reduction of steam
production
Drain malfunction
User parameter error
Supply water high conductivity
pre-alarm
External command signal not
properly connected
(only 2/10V)
Cylinder full with steam pro-
duction not in progress
Foam inside the cylinder
Cylinder almost completely
depleted
Red LED
fl a shes
2x long
3x long
4x long
5x long
6x long
7x long
8x long
9x long
10xlong
11xlong
Remedy
Do maintenance or replace the cylinder.
1. Check that the fi ll pipe from the mains to the humidifi er and
the internal pipe are not blocked or bent and that there is
suffi cient supply pressure (1-8 bar).
2. Check that the fi ll valve is properly working.
3. Check whether the counter-pressure onto the steam hose
is higher than the maximum limit, preventing the entry of
supply water into the cylinder by gravity.
4. Check that the steam outlet pipe is not choked and that
there is no condensate inside.
1. Cylinder completely depleted or excessive foam. Do main-
tenance to the cylinder.
1. Check the drain circuit and the proper operation of the drain
valve.
1. Download the proper default confi guration from HumiSet.
2. If the problem persists, contact APC customer service.
1. Check the conductivity of the supply water.
2. If necessary install a suitable demineralizer.
Note: The problem will not be solved by softening the supply
water.
1. Check the connection to the (external) controller.
With the humidifi er switched off:
1. Check for any leaks from the fi ll valve or the condensate
return pipe.
2. Check that the level sensors are clean.
Foam is usually caused by surfactants in the water (lubri-
cants, solvents, detergents, water treatment agents, soften-
ers) or an excessive concentration of dissolved salts:
1. Drain and clean the water supply pipes.
2. Clean the cylinder.
3. Check for the presence of softeners. (In this case, use
another type of supply water or reduce the softening)
Do maintenance and/or replace the cylinder.
Type
warning
disabling
disabling
disabling
blocking
warning
disabling
disabling
warning
warning
Reset
manual
manual
manual
manual
manual
display:
auto-
matic
reset
alarm:
automat.
manual
display:
manual
reset
display:
manual
reset
Alarm-
relay
not
active
active
active
active
active
not
active
active
active
not
active
not
active
Table 2 - Alarms (continued)
Note: "manual reset" means one of the following activities:
- pulling off and putting on the power supply plug G/G0 (see 9.1.5 operation - fi g. 1 on page 57)
- switch off the cooling unit by the main switch, switch off and on the control fuses F02