InRoom CW/DX – Operating Instructions
Tem peratur maximal 104°F maximal 40°C
Druck 14.5 - 116 psi 1 - 8 bar
55
Supply water - application limits
Tem perature
Pressure
Water properties and ingredients min max
hydrogen ions 7 8,5
specifi c conductivity (at 20°C)
σ
R, 20°C
µS/cm 300 1250
total dissolved solids TDS mg/l * *
dry residue at 180°C R
180
mg/l * *
total hardness mg/l CaCO
3
100
2
400
iron + manganese mg/l Fe + Mn 0 0,2
chlorides ppm Cl 0 30
silica mg/l SiO
2
0 20
residual chlorine mg/l Cl¯ 0 0,2
calcium sulphate mg/l CaSO
4
0 100
metallic impurities mg/l 0 0
solvents, diluents, soaps, lubricants mg/l 0 0
* values depending on specifi c conductivity; in general: TDS 0,93 • σ
20
; R
180
0,65 • σ
20
2
not lower than 200% of chlorides content in mg/l of Cl¯
9.1.3 Supply connections
The steam humidifi er is installed and electrically connected in the InRoom CRAC at the factory. Follow local,
state and national codes when attaching water lines.
Water supply
The water connection is made from the cold water supply and is to be equipped with a shut-off valve. Install a
fi l ter to retain solid particles. The humidifi er can be connected directly to the supply by a threaded tenon of 3/4
inch when the water pressure is between 1 and 8 bar (14.5 and 116 psi). The pipe should have a diameter of
at least 1/4 inch (6 mm). If the line pressure is more than 8 bar (116 psi), the connection must be made with
a pressure reducing valve (set to 4-6 bar [60-85 psi]). In each case ensure that the manufactured water pipe
upstream of the connection to the humidifi er is ushed properly. We recommend only using copper pipes.
The water supply temperature must not exceed 40
°C (104 °F).
Caution:
Do not treat the water with softeners.
This could result in corrosion of the electrodes and in the formation of foam with conside-
rable operational interruptions.
Prevent:
1. The use of well water, process water or water of cooling circuits and generally chemically
or bacteriologically polluted water.
2. The addition of disinfectants or anti-corrosion liquids, as these are very irritating for the
respiratory ducts.