InRoom CW/DX – Operating Instructions 13
ACW-System
The ACW system is a combination of
both the ”A” and ”CW” systems with two
cooling coils. The controller manages
the ACW system to allow the air cooled
”A” system to operate as standby to the
”CW” chilled water system or vice versa
to give added security and back up to
the computer room.
NOTE: Both systems may not run si-
multaneously. This can be prevented
by defi ning a cooling priority at the
controller.
GCW-System
The GCW system is a combination of
both the ”G” and ”CW” systems with two
cooling coils. The controller manages
the GCW system to allow the glycol
cooled or condenser water ”G” system
to operate
as standby to the ”CW” chilled water
system or vice versa to give added
security and back up to the computer
room.
NOTE: Both systems may not run si-
multaneously. This can be prevented
by defi ning a cooling priority at the
controller.
CW-System
When a central chilled water system is
the appropriate method of heat rejection,
cooling units are available in a packaged
fan-coil design.
Room air is recirculated through the cooling
coil, which transfers the heat load directly
into the chilled water ring main. Water fl ow
rate is regulated by a 2 or 3-way chilled
water valve, controlled by the controller, to
precisely maintain conditions in the critical
space.