6.4 Electrical connection
insertion for the power
supply cable
Electrical Hazard:
Disconnect all power sources before making electrical connections.
Only authorized personnel may connect electrical power.
This unit must be connected to earth ground.
The power supply system on site and the pre-fuses must be designed for the total current of the unit (see
technical data, beginning on page 24).
Route the electric cable into the electrics box from below and connect the three phases to the main switch,
the PE conductor at the PE rail and the neutral conductor at the neutral terminal, in accordance with the
wiring diagram (part of the unit documents).
Electrical Hazard:
The unit is designed for clockwise phase rotation.
The scroll compressor is dependent on correct phase rotation. The sense of rotation will be checked at
the factory before dispatch. On site, if the rotating fi eld of the compressor is incorrect, it must be corrected
by changing two phases of the power supply at the isolator. An inverse rotating fi eld can be detected by a
raised compressor noise level and can result in overheating and destruction of the compressor after several
hours of operation.
Electrical Hazard:
If using a Residual Current Device (RCD), take EN 50178 into account. Only type B pulse-
current FI circuit breakers are permitted. FI circuit breakers only provide equipment pro-
tection and are not intended to protect personnel.
Make sure that the power supply corresponds to the indications on the rating plate and that the
tolerances according to the "Application limits" are not exceeded.
In addition to this, the asymmetry of phase between the conductors may amount to 2% maximum.
The asymmetry of phase is determined by measuring the voltage difference between the phase
conductors. The average value of the voltage differences may not exceed 8 V.