34001813EN/AF - Page 54
4. Maintenance
4.4 Return to the normal position
Single UPS
Frequency converter
1 - Check that bypass switch Q3BP (10) is ON and that all other switches
are OFF.
2 - Set input switch Q4S (9) to ON.
3 - Set output switch Q5N (11) to ON.
4 - Wait until the display goes on and check that there are no faults on the
static-switch on the bypass line.
5 - Set bypass switch Q3BP (10) to OFF.
6 - Set the input circuit-breaker Q1 (8) to ON.
7 - Set the battery circuit-breaker QF1 (13) (or set the battery circuit-
breakers of the auxiliary cabinets if any) to ON.
The UPS unit starts automatically.
LED (31) is ON.
If LED (31) remains OFF, press the ON button (37)
(the system is in manual start mode).
If LED (31) still remains OFF and either of LEDs (32) or (33) is ON, a fault
has occurred (see section 4.1).
1 - Check that all switches are set to OFF.
2 - Set the input circuit-breaker Q4S (9) to ON (check that no cable is
connected on phase 1, phase 2 and phase 3).
3 - Set the input circuit-breaker Q1 (8) to ON.
4 - Set output switch Q5N (11) to ON.
5 - Set the battery circuit-breaker QF1 (13) (or set the battery circuit-
breakers of the auxiliary cabinets if any) to ON.
6 - Press the ON button (37).
If LED (31) still remains OFF and either of LEDs (32) or (33) is ON, a fault
has occurred (see section 4.1).