3. Operation
3.9 Relay contacts (communications card)
The indications 1.X become 2.X for a second identical card in the UPS.
Contacts are of the NO (normally open) type.
Inputs Factory setting Options (available on all contacts)
1.A
UPS ON
- Room temperature fault
- Transfer to bypass disabled
- Transfer to bypass disabled if Bypass AC source out of tolerance
- Desynchronise UPS from Bypass AC source
1.B
UPS OFF
Outputs Factory setting Options (available on all contacts)
1.1
General alarm
- Overload
- PFC fault
- Inverter fault
- Charger fault
- Automatic-bypass fault
- Bypass AC source out of tolerance
- Battery-temperature fault
- Fan fault
- Emergency power off activated
- Battery circuit breaker(s) open (at least one)
- Phase-sequence fault on normal or Bypass AC
source
- Blown fuse(s)
- Transfer to Bypass AC source disabled
- Operation in ECO mode
- UPS on manual bypass
1.2
Battery fault
1.3
Load on NORMAL source
1.4
Load on automatic bypass
1.5
Load on battery power
1.6
Low battery warning