9InfraStruXure Power Distribution Unit 40kW Instructions for Electricians
Connect an Emergency Power Off (EPO) switch
1. Connect the switch to the EPO connection point terminals located on the bottom side of the PDU user
connection plate. Read the label next to the terminal block to determine which terminals to connect to for
the signal type you are using:
–Contact ClosureNormally Open
–Contact ClosureNormally Closed
–24 Vac/VdcNormally Open
1 234
AT S E N
AT S 0
AT S 1
AT S 2
EPO
Contact
+
EPO 24V
AC/DC
Contact Inputs
Contact Outputs
USER INTERFACE
© 2001 APC
MADE IN U SA
pdx0202a
External set of
Normally Open Dry Contacts
1 234
AT S E N
AT S 0
AT S 1
AT S 2
EPO
Contact
+
EPO 24V
AC/DC
Contact Inputs
Contact Outputs
USER INTERFACE
© 2001 APC
MADE IN USA
pdx0203a
External set of
Normally Closed Dry Contacts
1 234
ATS EN
ATS 0
AT S 1
ATS 2
EPO
Contact
+
EPO 24V
AC/DC
Contact Inputs
Contact Outputs
USER INTERFACE
© 2001 APC
MADE IN USA
pdx0204a
24V AC or DC Power Supply
External set of
Normally Open Dry Contacts
Zobrazit stránku 12