InfraStruXure Power Distribution Unit 40kW Instructions for Electricians 8
Connect input conductors
Electrical Hazard: A licensed electrician must connect input conductors to the PDU!
At the Main Input switch, connect the input wiring according to the labels on the switch and the illustrations
below. See the table “Torque specs and tools required” on page 3 for specific information about connecting to
each terminal.
Warning: Connect the conductors to the terminals according to the labels on the terminals.
Use copper conductors only.
208/480/600 V input with a transformer:
3-phase, 3-wire + ground + GEC to a
suitable grounding electrode
208 V input without a transformer:
208 V, 3-phase, 4-wire + ground
GEC
G
L1
L2
L3
pdx0150c
G
L1
L2
L3
N
pdx0149e