APC Network Management Card AP9617 Uživatelská příručka Strana 59

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 190
  • Tabulka s obsahem
  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 58
®
®®
®
USERS GUIDE
network management card
52
Syslog Server Settings
Server IP Uses specific IP addresses to Identify which of up to four servers will
receive Syslog messages sent by the Management Card.
N
OTE: To use the Syslog feature, at least Server IP must be defined
for at least one server.
Port Identifies the user datagram protocol (UDP) port that the Management
Card will use to send Syslog messages. The default is 514, the
number of the UDP port assigned to Syslog.
Local Priority (Severity Mapping)
Map to
Syslogs
Priorities
Maps each of the severity levels (Local Priority settings) that can be
assigned to UPS, environmental monitor, and Management Card
events to the available Syslog priorities. The following definitions are
from RFC3164:
Emergency: The system is unusable
Alert: Action must be taken immediately
Critical: Critical conditions
Error: Error conditions
Warning: Warning conditions
Notice: Normal but significant conditions
Informational: Informational messages
Debug: Debug-level messages
Following are the default settings for the four Local Priority settings:
Severe is mapped to Critical
Warning is mapped to Warning
Informational is mapped to Info
None (for events that have no severity level assigned) is mapped to
Info
N
OTE: To disable sending Syslog messages for Severe, Warning, or
Informational events, see Event Actions (Web Interface Only).