UPS Surge Overload Time
Reset to Factory Default
Circuits Configuration and Setup
Press the Circuit Setup button to enter Circuit Setup mode. When the circuit setup messages are displayed
they appear in the same order as they are listed in this section.
Circuit Setup
Circuit setup begins with Circuit 1, and proceeds through all of the configuration settings for Circuit 1
before moving on to Circuit 2, the same is true for Circuit 2, then Circuit 3, and so on.
This value is used to determine the response speed of the
ALM algorithm. When the power output from the UPS source
surge exceeds the power rating (set earlier in this section) for
the specified
UPS SRGE OVERLD TIME (a value in the
[0-60] SEC range), then load shedding will be activated.
Load shedding occurs when the rated output power of the
UPS is exceeded for longer than the
SRGE OVERLD TIME.
Note If you reduce the surge overload time it reduces the likelihood that the UPS will be
overloaded, but it increases the chance that load shedding will occur.
If you increase the surge overload time it increases the likelihood that the UPS will
be overloaded, but decreases the chance that load shedding will occur.
Select
YES to reset all configurable parameters to the factory
default. Selecting
YES also restarts the UTS Setup Wizard,
which is described in Initial Setup in the Universal Transfer
Switch Site Preparation and Installation Guide (Document
No. 990-2992A).
Note Use the Up Arrow and Down Arrow buttons to move between displays, and to
change settings. Also, note that settings change immediately as soon as the Up
Arrow or Down Arrow button is pressed.
Note To configure a particular circuit, use the Circuit Status button and change the
display to show the desired circuit (for example, CKT3), then press the Circuit
Setup button. The setup screen for that particular circuit will be displayed.
UPS SRGE OVERLD TIME
[0-60] SEC
!
RESET TO DEFAULT
NO/YES
!
!