50 Implementing UPS Configurations with Microsoft Cluster Server
Figure 49. Single UPS Run Command File — Low Battery Condition
7. In the Event Actions window, select Low Battery Condition.
a. Select the Run Command File checkbox and click Options.
b. In the pop-up window, enter the following in the Command File field:
“C:\UPS_CMD\UPS.CMD” SingleUPSOnBattery >> C:\UPS_CMD\LOG.TXT
c. Set Wait to 0 seconds. A low battery condition means that the UPS can
supply the systems for a short period only and immediate actions must take
place. This wait time forces immediate execution of the command file when
a low battery condition occurs. Click the OK button to apply your choices.
Figure 50. Single UPS Event Actions