Strany 1 - User Guide

User GuideMetered-by-Outlet With SwitchingRack Power Distribution UnitAP86XX

Strany 2 - Contents

1Metered-by-Outlet With Switching Rack PDU User GuideIntroductionProduct FeaturesThe APC by Schneider Electric Metered-by-Outlet with Switching Rack P

Strany 3

91Metered-by-Outlet With Switching Rack PDU User GuideFTP Server Path: Administration > Network > FTP ServerThe FTP Server settings enable (by d

Strany 4

Metered-by-Outlet With Switching Rack PDU User Guide92Administration: NotificationEvent Actions Path: Administration > Notification > Event Acti

Strany 5

93Metered-by-Outlet With Switching Rack PDU User GuideConfigure by event. To define event actions for an individual event:1. Select the Administration

Strany 6

Metered-by-Outlet With Switching Rack PDU User Guide94Active, Automatic, Direct NotificationE-mail notificationOverview of setup. Use the Simple Mail

Strany 7

95Metered-by-Outlet With Switching Rack PDU User GuideE-mail test. Path: Administration > Notification > E-mail > testSend a test message to

Strany 8

Metered-by-Outlet With Switching Rack PDU User Guide96SNMP trapsTrap Receivers. Path: Administration > Notification > SNMP Traps > trap recei

Strany 9

97Metered-by-Outlet With Switching Rack PDU User GuideRemote Monitoring ServicePath: Administration > Notification > Remote MonitoringThe APC Re

Strany 10 - Introduction

Metered-by-Outlet With Switching Rack PDU User Guide98Syslog settings. Path: Logs > Syslog > settingsSyslog test and format example. Path: Logs

Strany 11 - Types of User Accounts

99Metered-by-Outlet With Switching Rack PDU User GuideAdministration: General OptionsIdentification Path: Administration > General > Identificat

Strany 12 - Network Port Sharing

Metered-by-Outlet With Switching Rack PDU User Guide100Daylight saving Path: Administration > General > Date & Time > daylight savingEnab

Strany 13 - Getting Started

Metered-by-Outlet With Switching Rack PDU User Guide2Access Priorities for Logging onOnly one user at a time can log on to the Rack PDU. The priority

Strany 14 - Establish Network Settings

101Metered-by-Outlet With Switching Rack PDU User GuideEvent Log and Temperature UnitsPath: Administration > General > PreferencesColor-code eve

Strany 15 - 04) is the length

Metered-by-Outlet With Switching Rack PDU User Guide102Configure Links Path: Administration > General > Quick LinksSelect the Administration tab

Strany 16 - Command Line Interface

103Metered-by-Outlet With Switching Rack PDU User GuideDevice IP Configuration WizardCapabilities, Requirements, and InstallationHow to use the Wizard

Strany 17

Metered-by-Outlet With Switching Rack PDU User Guide104Run the Wizard to perform the configuration. To discover and configure the unconfigured Rack PD

Strany 18 - Rack PDU Front Panel

105Metered-by-Outlet With Switching Rack PDU User GuideHow to Export Configuration SettingsRetrieving and Exporting the .ini FileSummary of the proced

Strany 19 - Item Function

Metered-by-Outlet With Switching Rack PDU User Guide106Detailed proceduresRetrieving. To set up and retrieve an .ini file to export:1. If possible, us

Strany 20

107Metered-by-Outlet With Switching Rack PDU User GuideTransferring the file to a single Rack PDU. To transfer the .ini file to another Rack PDU, do e

Strany 21

Metered-by-Outlet With Switching Rack PDU User Guide108The Upload Event and Error MessagesThe event and its error messagesThe following event occurs w

Strany 22 - Load indicator LED

109Metered-by-Outlet With Switching Rack PDU User GuideFile TransfersHow to Upgrade FirmwareBenefits of upgrading firmwareWhen you upgrade the firmwar

Strany 23

Metered-by-Outlet With Switching Rack PDU User Guide110Using the Firmware Upgrade UtilityThis Firmware Upgrade Utility is part of the firmware upgrade

Strany 24 - About the Main Screen

3Metered-by-Outlet With Switching Rack PDU User GuideWatchdog FeaturesOverviewTo detect internal problems and recover from unanticipated inputs, the R

Strany 25

SCP. To use Secure CoPy (SCP) to upgrade firmware for the Rack PDU, follow these steps (this procedure assumes bootmon does not need upgrading, it is

Strany 26 - Command Syntax

Metered-by-Outlet With Switching Rack PDU User Guide112How to upgrade multiple Rack PDUsFirmware Upgrade Utility. Use this for multiple firmware updat

Strany 27 - Command Response Codes

113Metered-by-Outlet With Switching Rack PDU User GuideIf you are unsure whether to upgrade any particular module, then upgrading all three is recomme

Strany 28

Metered-by-Outlet With Switching Rack PDU User Guide114Verifying Upgrades and UpdatesVerify the success or failure of the transferTo verify whether a

Strany 29

115Metered-by-Outlet With Switching Rack PDU User GuideTroubleshootingRack PDU Access ProblemsFor problems that persist or are not described here, see

Strany 30 - Access: Administrator only

Metered-by-Outlet With Switching Rack PDU User Guide116Appendix A: List of Supported CommandsNetwork Management Card Command Descriptions?aboutalarmco

Strany 31

117Metered-by-Outlet With Switching Rack PDU User Guideradius [-a <local | radiusLocal | radius> (Access)][-p1 <primary server>][-s1 <p

Strany 32

Metered-by-Outlet With Switching Rack PDU User Guide118Device Command DescriptionsbkLowLoad[[id#:]<“all” | bank#> <current>]bkNearOver[[id

Strany 33

119Metered-by-Outlet With Switching Rack PDU User GuideolNearOver[[id#:]<“all” | outlet#> <power>]olOff[[id#:]<“all” | outlet name | ou

Strany 34

Metered-by-Outlet With Switching Rack PDU User Guide120userDelete[<user>]userListuserPasswd[<user> <new password> <new password&g

Strany 35

Metered-by-Outlet With Switching Rack PDU User Guide4Specific assignment of Display IDs. Follow the instructions below before powering up any of the R

Strany 36

10/2012990-3431C-001APC Worldwide Customer SupportCustomer support for this or any other APC product is available at no charge in any of the following

Strany 37

5Metered-by-Outlet With Switching Rack PDU User GuideEstablish Network SettingsNote: Disregard the procedures described in this section if you have St

Strany 38

Metered-by-Outlet With Switching Rack PDU User Guide6When the Rack PDU reboots, the BOOTP server provides it with the TCP/IP settings.• If you specif

Strany 39 - Access: Administrator only

7Metered-by-Outlet With Switching Rack PDU User GuideCommand Line Interface1. Log on to the command line interface. See “Log on to the Command Line In

Strany 40

Metered-by-Outlet With Switching Rack PDU User Guide8Recovering from a Lost PasswordYou can use a local computer (a computer or other device that conn

Strany 41

9Metered-by-Outlet With Switching Rack PDU User GuideRack PDU Front PanelNote: Your APC product is configured so the display backlight turns off after

Strany 42

Metered-by-Outlet With Switching Rack PDU User Guide10Item FunctionOK, Warning, Overload LED Indicates the status of the Rack PDU load. See “Load ind

Strany 43

ContentsMetered-by-Outlet With Switching Rack PDU User Guide iIntroduction ... 1Prod

Strany 44

11Metered-by-Outlet With Switching Rack PDU User GuideExample: AP8661 Display Tree page 1

Strany 45

Metered-by-Outlet With Switching Rack PDU User Guide12Example: AP8661 Display Tree page 2

Strany 46

13Metered-by-Outlet With Switching Rack PDU User GuideNetwork Status LED10/100 LEDLoad indicator LEDThe load indicator LED identifies overload and war

Strany 47

Metered-by-Outlet With Switching Rack PDU User Guide14Command Line InterfaceAbout the Command Line InterfaceYou can use the command line interface to

Strany 48

15Metered-by-Outlet With Switching Rack PDU User GuideLocal access to the command line interfaceFor local access, use a computer that connects to the

Strany 49

Metered-by-Outlet With Switching Rack PDU User Guide16• A Stat field reports the Rack PDU status.Stat : P+ N4+ N6+ A+Note: If P+ is not displayed, con

Strany 50

17Metered-by-Outlet With Switching Rack PDU User GuideCommand SyntaxExample of a command that supports multiple options: user [-an <admin name>]

Strany 51

Metered-by-Outlet With Switching Rack PDU User Guide18Command Response CodesThe command response codes enable scripted operations to detect error cond

Strany 52

19Metered-by-Outlet With Switching Rack PDU User GuideNetwork Management Card Command DescriptionsAccess: Administrator, Device User, Outlet UserDescr

Strany 53

Metered-by-Outlet With Switching Rack PDU User Guide20bootAccess: Administrator onlyDescription: Define how the Rack PDU will obtain its network setti

Strany 54

Metered-by-Outlet With Switching Rack PDU User GuideiiLog on to the Command Line Interface . . . . . . . . . . . . . . . . . . . . . . 14Remote access

Strany 55

21Metered-by-Outlet With Switching Rack PDU User GuideconsoleAccess: Administrator onlyDescription: Define whether users can access the command line i

Strany 56

Metered-by-Outlet With Switching Rack PDU User Guide22dateAccess: Administrator onlyDefinition: Configure the date used by the Rack PDU.To configure

Strany 57

23Metered-by-Outlet With Switching Rack PDU User GuidednsAccess: Administrator onlyDefinition: Configure the manual Domain Name System (DNS) settings

Strany 58

Metered-by-Outlet With Switching Rack PDU User Guide24FTPAccess: Administrator onlyDescription: Enable or disable access to the FTP server. Optionally

Strany 59

25Metered-by-Outlet With Switching Rack PDU User GuidepingAccess: Administrator, Device UserDescription. Determine whether the device with the IP add

Strany 60

Metered-by-Outlet With Switching Rack PDU User Guide26radiusAccess: Administrator onlyDescription: View the existing RADIUS settings, enable or disabl

Strany 61 - Example:

27Metered-by-Outlet With Switching Rack PDU User GuideresetToDefAccess: Administrator onlyDescription: Reset all parameters to their default.Example:

Strany 62 - Web Interface

Metered-by-Outlet With Switching Rack PDU User Guide28tcpipAccess: Administrator onlyDescription: View and manually configure these network settings f

Strany 63 - URL address formats

29Metered-by-Outlet With Switching Rack PDU User GuideuserAccess: Administrator onlyDescription: Configure the user name, password, and inactivity tim

Strany 64 - Web Interface Features

Metered-by-Outlet With Switching Rack PDU User Guide30xferINIAccess: Administrator onlyDescription: Use XMODEM to upload an INI file while you are acc

Strany 65 - Other Web interface features

Metered-by-Outlet With Switching Rack PDU User Guide iiiDevice Command Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31Network

Strany 66

31Metered-by-Outlet With Switching Rack PDU User GuideDevice Command DescriptionsNetwork Port Sharing CommandsThe Command Line Interface allows comman

Strany 67

Metered-by-Outlet With Switching Rack PDU User Guide32bkOverLoadAccess: Administrator, Device UserDescription: Set or view the bank overload threshold

Strany 68 - About the Home Tab

33Metered-by-Outlet With Switching Rack PDU User GuidedevLowLoadAccess: Administrator, Device UserDescription: Set or view the low-load threshold in k

Strany 69 - Device Management

Metered-by-Outlet With Switching Rack PDU User Guide34devReadingAccess: Administrator, Device UserDescription: View the total power in kilowatts or to

Strany 70 - Reset Peak Load and kWh

35Metered-by-Outlet With Switching Rack PDU User GuidehumLowAccess: Administrator, Device UserDescription: Set or view the low humidity threshold as a

Strany 71 - Outlet group terminology

Metered-by-Outlet With Switching Rack PDU User Guide36olAssignUsrAccess: AdministratorDescription: Assign control of outlets to an outlet user that ex

Strany 72

37Metered-by-Outlet With Switching Rack PDU User GuideolDlyOffAccess: Administrator, Device User, and Outlet User, but only for outlets to which the u

Strany 73 - Create a local outlet group

Metered-by-Outlet With Switching Rack PDU User Guide38olDlyRebootAccess: Administrator, Device User, and Outlet User, but only for outlets to which th

Strany 74

39Metered-by-Outlet With Switching Rack PDU User GuideolGroupsAccess: Administrator, Device User, and Outlet User.Description: List the outlet synchro

Strany 75

Metered-by-Outlet With Switching Rack PDU User Guide40olLowLoadAccess: Administrator, Device UserDescription: Set or view the outlet low-load threshol

Strany 76 - Initiate a control action

Metered-by-Outlet With Switching Rack PDU User GuideivWeb Interface... 53Supported Web B

Strany 77 - Option Description

41Metered-by-Outlet With Switching Rack PDU User GuideolNearOverAccess: Administrator, Device UserDescription: Set or view the outlet near-overload th

Strany 78

Metered-by-Outlet With Switching Rack PDU User Guide42olOffDelayAccess: Administrator, Device User, and Outlet User, but only for outlets to which the

Strany 79 - Schedule Outlet Actions

43Metered-by-Outlet With Switching Rack PDU User GuideolOnDelayAccess: Administrator, Device User, and Outlet User, but only for outlets to which the

Strany 80 - Outlet Manager Menu

Metered-by-Outlet With Switching Rack PDU User Guide44olRbootTimeAccess: Administrator, Device User, and Outlet User, but only for outlets to which th

Strany 81 - Environment

45Metered-by-Outlet With Switching Rack PDU User GuideolRebootAccess: Administrator, Device User, and Outlet User, but only for outlets to which the u

Strany 82 - Use the Event and Data Logs

Metered-by-Outlet With Switching Rack PDU User Guide46olUnasgnUsrAccess: AdministratorDescription: Remove control of outlets from an outlet user that

Strany 83

47Metered-by-Outlet With Switching Rack PDU User GuidephNearOverAccess: Administrator, Device UserDescription: Set or view the phase near-overload thr

Strany 84 - Data log

Metered-by-Outlet With Switching Rack PDU User Guide48phReadingAccess: Administrator, Device UserDescription: View the current, voltage, or power for

Strany 85

49Metered-by-Outlet With Switching Rack PDU User GuideprodInfoAccess: Administrator, Device User, Outlet UserDescription: View information about the R

Strany 86

Metered-by-Outlet With Switching Rack PDU User Guide50tempHighAccess: Administrator, Device UserDescription: Set or view the high-temperature threshol

Strany 87 - Administration: Security

Metered-by-Outlet With Switching Rack PDU User Guide vConfigure and Control Outlet Groups. . . . . . . . . . . . . . . . . . . . . . . .62Outlet group

Strany 88

51Metered-by-Outlet With Switching Rack PDU User GuideuserAddAccess: AdministratorDescription: Add an outlet user to the local user database.Example:

Strany 89 - Configure the RADIUS Server

Metered-by-Outlet With Switching Rack PDU User Guide52whoamiAccess: Administrator, Device User, Outlet UserDescription: View the user name of the acti

Strany 90 - Inactivity Timeout

53Metered-by-Outlet With Switching Rack PDU User GuideWeb InterfaceSupported Web BrowsersYou can use Microsoft® Internet Explorer® (IE) 7.x and higher

Strany 91 - TCP/IP settings

Metered-by-Outlet With Switching Rack PDU User Guide54URL address formatsType the DNS name or IP address of the Rack PDU in the Web browser’s URL addr

Strany 92 - DHCP response options

55Metered-by-Outlet With Switching Rack PDU User GuideWeb Interface FeaturesRead the following to familiarize yourself with basic Web interface featur

Strany 93 - Ping Response

Metered-by-Outlet With Switching Rack PDU User Guide56Quick LinksAt the lower left on each page of the interface, there are three configurable links.

Strany 94

57Metered-by-Outlet With Switching Rack PDU User GuideNetwork Port Sharing on the Web InterfaceGroup Control using Network Port SharingThe web interfa

Strany 95

Metered-by-Outlet With Switching Rack PDU User Guide58Most of the web pages under the Home, Device Manager, and Environment tabs allow you to switch b

Strany 96 - Console

59Metered-by-Outlet With Switching Rack PDU User GuideAbout the Home TabUse the Home tab to view active alarms, the load status of the Rack PDU, and t

Strany 97

Metered-by-Outlet With Switching Rack PDU User Guide60Device ManagementAbout the Device Manager TabPath: Device ManagerUse the Device Manager tab to:•

Strany 98

Metered-by-Outlet With Switching Rack PDU User GuideviConfigure the RADIUS Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80Summar

Strany 99

61Metered-by-Outlet With Switching Rack PDU User GuideConfigure the Name and Location of the Rack PDUPath: Device Manager > Device LoadThe name and

Strany 100 - FTP Server

Metered-by-Outlet With Switching Rack PDU User Guide62Set the Overload Outlet RestrictionsPath: Device Manager > Phase Load and Bank LoadPrevent us

Strany 101 - Administration: Notification

63Metered-by-Outlet With Switching Rack PDU User GuidePurpose and benefits of outlet groupsBy using groups of synchronized outlets on Rack PDUs, you c

Strany 102

Metered-by-Outlet With Switching Rack PDU User Guide64Enable outlet groupsClick the Device Manager tab and select Group Configuration from the Outlet

Strany 103 - E-mail notification

65Metered-by-Outlet With Switching Rack PDU User GuideCreate multiple global outlet groupsTo set up multiple global outlet groups that link to outlet

Strany 104 - Setting Description

Metered-by-Outlet With Switching Rack PDU User Guide66Typical outlet group configurationsThe following configuration shows two Rack PDUs, each with ei

Strany 105 - SNMP Trap Test

67Metered-by-Outlet With Switching Rack PDU User GuideVerify your setup and configuration for global outlet groupsTo ensure that your setup meets all

Strany 106 - Remote Monitoring Service

Metered-by-Outlet With Switching Rack PDU User Guide68Control actions you can select. Option DescriptionNo Action Do nothing.On Immediate Apply power

Strany 107 - Syslog settings

69Metered-by-Outlet With Switching Rack PDU User GuideConfigure outlet settings and the outlet nameThe following settings are available:To configure o

Strany 108 - Set the Date and Time

Metered-by-Outlet With Switching Rack PDU User Guide70Schedule Outlet ActionsActions you can scheduleTo configure values for Power On Delay, Power Off

Strany 109 - Use an .ini File

Metered-by-Outlet With Switching Rack PDU User Guide viiSet the Date and Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Strany 110 - Reset the Rack PDU

71Metered-by-Outlet With Switching Rack PDU User GuideEdit, disable, enable, or delete a scheduled outlet event1. At the Web interface, select the Dev

Strany 111 - About the Rack PDU

Metered-by-Outlet With Switching Rack PDU User Guide72EnvironmentConfigure Temperature and Humidity SensorsPath: EnvironmentThrough the Environment ta

Strany 112 - Use the Wizard

73Metered-by-Outlet With Switching Rack PDU User GuideLogsUse the Event and Data LogsEvent logPath: Logs > Events > optionsYou can view, filter,

Strany 113

Metered-by-Outlet With Switching Rack PDU User Guide74To filter the log (Logs > Events > log): • Filtering the log by date or time: To display t

Strany 114 - INI and Network Port Sharing

75Metered-by-Outlet With Switching Rack PDU User GuideData logPath: Logs > Data > optionsThe data log records the current and power for the devi

Strany 115 - Detailed procedures

Metered-by-Outlet With Switching Rack PDU User Guide76To configure data log rotation (Logs > Data > rotation): Set up a password-protected data

Strany 116

77Metered-by-Outlet With Switching Rack PDU User GuideUse FTP or SCP to retrieve log filesAn Administrator or Device User can use FTP or SCP to retrie

Strany 117 - Related Topics

Metered-by-Outlet With Switching Rack PDU User Guide78Administration: SecurityLocal UsersSet user accessPath: Administration > Security > Local

Strany 118 - File Transfers

79Metered-by-Outlet With Switching Rack PDU User GuideSelect one of the following:• Local Authentication Only: RADIUS is disabled. Local authenticatio

Strany 119

Metered-by-Outlet With Switching Rack PDU User Guide80Configure the RADIUS ServerSummary of the configuration procedureYou must configure your RADIUS

Strany 120

Metered-by-Outlet With Switching Rack PDU User GuideviiiFile Transfers... 109How to Upgrad

Strany 121

81Metered-by-Outlet With Switching Rack PDU User GuideRADIUS and Network Port SharingNote: See the Security Handbook for APC Network Management Cards

Strany 122

Metered-by-Outlet With Switching Rack PDU User Guide82Administration: Network FeaturesTCP/IP and Communication SettingsTCP/IP settings Path: Administr

Strany 123 - Last Transfer Result codes

83Metered-by-Outlet With Switching Rack PDU User GuideDHCP response optionsEach valid DHCP response contains options that provide the TCP/IP settings

Strany 124 - Troubleshooting

Metered-by-Outlet With Switching Rack PDU User Guide84Path: Administration > Network > TCP/IP > IPv6 settingsPort Speed Path: Administration

Strany 125

85Metered-by-Outlet With Switching Rack PDU User GuideDNS Path: Administration > Network > DNS > optionsUse the options under DNS to configur

Strany 126

Metered-by-Outlet With Switching Rack PDU User Guide86Web Path: Administration > Network > Web > optionsOption Descriptionaccess To activate

Strany 127 - Device Command Descriptions

87Metered-by-Outlet With Switching Rack PDU User GuideConsole Path: Administration > Network > Console > optionsNote: To use SSH, you must ha

Strany 128

Metered-by-Outlet With Switching Rack PDU User Guide88SNMPAll user names, passwords, and community names for SNMP are transferred over the network as

Strany 129

89Metered-by-Outlet With Switching Rack PDU User GuideSNMPv1 Path: Administration > Network > SNMPv1 > optionsOption Descriptionaccess Enable

Strany 130 - 990-3431C-001

Metered-by-Outlet With Switching Rack PDU User Guide90SNMPv3 Path: Administration > Network > SNMPv3 > optionsFor SNMP GETs, SETs, and trap r