For more information about all APC products, go to www.apc.com
Symmetra 4-16kVA Configuration Guide
Step 2
Determine the part number based
on your current and future load
requirements.
Current kVA Future kVA
4 8 SY4KEX-PD SY4KEX SY4KEXI n/a SY4KEXJ
8 8 SY8K-PD SY8K SY8KI n/a SY8KJ
8 16 SY8KEX-PD SY8KEX SY8KEXI SY8KEX3I SY8KEXJ
12 16 SY12KEX-PD SY12KEX SY12KEXI SY12KEX3I SY12KEXJ
16 16 SY16K-PD SY16K SY16KI SY16K3I SY16KJ
For more info see page 10 10 11 11 12
Step 1
Use your input and output requirements
to determine the correct Symmetra
product family.
Step 3
Add redundancy
(N+1): Purchase
an additional
Power Module
(SYPM).
Step 5
Determine Manageability and Accessory
requirements (see page 9)
_____ SmartSlot Accessories (up to 3 additional)
_____ Other Options _____ PDUs
Step 6
Determine Serviceability requirements (see page 19)
_____ Extended Warranty _____ On-Site Service
_____ System Start-up _____ Network Integration
Unit scalable to Load Standard Std + (1) Std + (1) Std + (1) Std + (2) Std + (3) Std +(4)
kVA/kW configuration SYXR4B4 or SYXR8B12* SYXR12B12* SYXR12B12* SYXR12B12* SYXR12B12*
(1) SYXR4B12*
4 8kVA 2/1.4 15m 2.1h 4.3h 6.6h 14.2h 22.5h 31.3h
(2.8 5.6kW) 4/2.8 5m 56m 1.9h 3h 6.6h 10.5h 14.6h
8kVA 4/2.8 15m 1.1h 2.1h 3.2h 6.7h 10.5h 14.5h
(5.6kW) 6/4.2 8m 42m 1.3h 2h 4.3h 6.7h 9.3h
8/5.6 5m 29m 56m 1.4h 3.1h 4.8h 6.7h
8 16kVA 4/2.8 15m 1.1h 2.1h 3.1h 6.6h 10.3h 14.3h
(5.6 11.2kW) 6/4.2 8m 41m 1.3h 2h 4.2h 6.6h 9.2h
8/5.6 5m 29m 56m 1.4h 3h 4.8h 6.6h
12 16kVA 6/4.2 15m 49m 1.5h 2.1h 4.3h 6.7h 9.2h
(8.4 11.2kW) 8/5.6 10m 34m 1h 1.5h 3.1h 4.9h 6.7h
10/7 6m 26m 47m 1.1h 2.4h 3.8h 5.2h
12/8.4 5m 20m 38m 56m 1.9h 3.1h 4.2h
16kVA 8/5.6 15m 40m 1.1h 1.6m 3.2h 4.9h 6.7h
(11.2kW) 10/7 11m 30m 52m 1.3h 2.5h 3.8h 5.2h
12/8.4 8m 24m 42m 1h 2h 3.1h 4.3h
16/11.2 5m 16m 29m 42m 1.5h 2.2h 3.1h
MiniFrameMasterFrame
Step 4 Select the appropriate runtime for your application.
Input/Output considerations
Input voltage 208/240VAC 230VAC 400VAC (3-phase) 200VAC
Output voltage 120/208/240VAC 230VAC 230VAC 100/200VAC
Input/Output 60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
frequency
Output connections Hardwire Hardwire only Hardwire only Hardwire only Hardwire only
and outlets
Optional Module
Included Module
4kVA Scalable to 8kVA, N+1
(2.8kW to 5.6 kW)
8kVA, N+1
(5.6 kW)
8kVA Scalable to 16kVA, N+1
(5.6 kW to 11.2 kW)
12kVA Scalable to 16kVA, N+1
(8.4 kW to 11.2 kW)
16kVA, N+1
(11.2 kW)
*See page 9 for correct extended run model number based on input voltage.