APC NetworkAIR™ AFX 27
Guide Specifications
PART 1 PART 1 GENERAL
1.01 SUMMARY
A. The environmental control system shall be designed specifically for precision temperature and
humidity control applications. It will automatically monitor and control heating, cooling,
humidifying, dehumidifying, and filtering functions for the conditioned space. The system
shall be built to the highest quality engineering and manufacturing standards, and shall be
floor mounted and configured for ________(up/down) discharge of conditioned airflow, with
draw-through air pattern, to provide uniform air distribution over the entire face of the coil.
1.02 DESIGN REQUIREMENTS
A. The system shall be as described in the following specification as manufactured by APC.
1. Model: ____________________________.
2. Total cooling capacity: _______________ MBH (kW).
3. Sensible cooling capacity: ____________ MBH (kW).
4. Return air temperature: _______________ º F (º C) DB.
5. Return air temperature: _______________ º F (º C) WB.
6. Humidity: __________________________% RH.
7. Air quantity: _______________________ CFM (L/s).
8. External Static Pressure _______________inches (Pa).
9. Humidifier capacity: _________________ lbs/hr (kg/hr).
10. Electrical supply: ________ V, _________ ph, 60 Hz.
1.03 SUBMITTALS
A. Submittals shall be provided with the proposal and shall include: capacity data, electrical data,
physical data, electrical connection drawing, and piping connection drawing.
1.04 QUALITY ASSURANCE
A. The system shall be completely factory-tested prior to shipment. Testing shall include, but not
be limited to: complete pressure and leak testing to ensure system integrity, “Hi-Pot” test, and
controls calibration and settings. Each system shall ship with a completed test report to verify
completion of factory testing procedure. The system shall be NTRL listed, MCA, and
electrical system shall be UL Listed to UL 1995 and CSA 22.2 No. 236.
1.05 WARRANTY
A. System parts shall be warranted for a period of 12months from date of shipment from factory.