Operation and
Maintenance
InRow
®
RD 10kW
Air Cooled
ACRD100
ACRD101
Zobrazit stránku 0
1 2 3 4 5 6 ... 55 56

Shrnutí obsahu

Strany 1 - Maintenance

Operation andMaintenanceInRow® RD 10kWAir CooledACRD100ACRD101

Strany 2 - 동봉된 CD 안에 한국어 매뉴얼이 있습니다

InRow RD 10 kW Air Cooled Operation and Maintenance2Safety Read and adhere to the following important safety considerations when working with this coo

Strany 3

3InRow RD 10 kW Air Cooled Operation and MaintenanceCommissioningWarning: APC authorized personnel must perform the following procedures.Electrical Ha

Strany 4

InRow RD 10 kW Air Cooled Operation and Maintenance4Electrical inspection checklistThe electrical inspection verifies that all electrical connections

Strany 5 - Contents

5InRow RD 10 kW Air Cooled Operation and MaintenanceMechanical inspection checklistThe mechanical inspection verifies that all mechanical components a

Strany 6

InRow RD 10 kW Air Cooled Operation and Maintenance6User interface inspection checklistThe user interface inspection verifies that the sensors and int

Strany 7

7InRow RD 10 kW Air Cooled Operation and MaintenanceCharging With RefrigerantCalculating R410A chargeUse the following table and formula when calculat

Strany 8

InRow RD 10 kW Air Cooled Operation and Maintenance8Quantity of R410A in 1/2 in OD liquid line: (area) x (length in ft) x (density): 0.0010554 (ft2) x

Strany 9 - General Information

9InRow RD 10 kW Air Cooled Operation and MaintenanceCharging the equipmentCaution: This procedure is to be done by APC-trained personnel only.R410A is

Strany 10

InRow RD 10 kW Air Cooled Operation and Maintenance10Compressor Oil ChargeCaution: This procedure is to be done by APC-trained personnel only.You may

Strany 11 - Commissioning

11InRow RD 10 kW Air Cooled Operation and Maintenance2. Prepare to add oil:a. Use a new, sealed oil can and a manual oil pump. The pump hose must be s

Strany 12

This manual is available in English on the enclosed CD.Dieses Handbuch ist in Deutsch auf der beiliegenden CD-ROM verfügbar.Deze handleiding staat in

Strany 13 - Ensure that the:

InRow RD 10 kW Air Cooled Operation and Maintenance12OperationDisplay InterfaceItem FunctionCritical Alarm LED (red) When lit, a critical alarm condi

Strany 14 - Final inspection checklist

13InRow RD 10 kW Air Cooled Operation and MaintenanceUsing the Display InterfaceEvery time power is applied to the cooling unit, the display interface

Strany 15 - Charging With Refrigerant

InRow RD 10 kW Air Cooled Operation and Maintenance14Navigating the main menuSelector arrow. Press the up or down arrow key to move the selector arrow

Strany 16 - °C (-20°F)

15InRow RD 10 kW Air Cooled Operation and MaintenanceUsing the Path statementSelect the main- and sub-menu options specified in the path statement to

Strany 17 - Charging the equipment

InRow RD 10 kW Air Cooled Operation and Maintenance16Stop the cooling unitPath: Main > On/StandbyPress the ENTER key to change the setting to Stand

Strany 18 - Compressor Oil Charge

17InRow RD 10 kW Air Cooled Operation and MaintenanceContactsView the state of input and output contactsPath: Main > Configure Unit > Discrete I

Strany 19

InRow RD 10 kW Air Cooled Operation and Maintenance18Type. Set the rack deployment strategy for the cooling units of this cooling group:• Spot: The co

Strany 20 - Operation

19InRow RD 10 kW Air Cooled Operation and MaintenanceControl the EnvironmentThe primary function of the cooling unit is to capture the heat generated

Strany 21 - Using the Display Interface

InRow RD 10 kW Air Cooled Operation and Maintenance20PID settingsPath: Main > Set Group PIDThe Proportional plus Integral plus Derivative (PID) loo

Strany 22 - Navigating the sub-menus

21InRow RD 10 kW Air Cooled Operation and MaintenanceTune the PID loopTune the PID loop to optimize the performance of the cooling group. Caution: Thi

Strany 23 - NTER key to select the

American Power Conversion Legal DisclaimerThe information presented in this manual is not warranted by the American Power Conversion Corporation to be

Strany 24 - General Configuration

InRow RD 10 kW Air Cooled Operation and Maintenance22Run hoursThe cooling unit records the number of hours each of its components has operated. When a

Strany 25 - Cooling Group Configuration

23InRow RD 10 kW Air Cooled Operation and MaintenanceDisplay SettingsSet display interface settings including the time and date, units of measure, pas

Strany 26 - Configure Modbus

InRow RD 10 kW Air Cooled Operation and Maintenance24Adjust display settingsPath: Main > Configure Display Contrast. Adjust the visibility of the s

Strany 27 - Control the Environment

25InRow RD 10 kW Air Cooled Operation and MaintenanceNetwork ConfigurationThe cooling unit is shipped with a Network Management Card that enables the

Strany 28 - PID settings

InRow RD 10 kW Air Cooled Operation and Maintenance26View Status ReadingsThe display interface has several options for viewing the status of the cooli

Strany 29 - Tune the PID loop

27InRow RD 10 kW Air Cooled Operation and MaintenanceCooling group statusPath: Main > View Group StatusView information about the cooling group.Coo

Strany 30 - Service intervals

InRow RD 10 kW Air Cooled Operation and Maintenance28Event LogThe event log saves status information and a message each time a change in the cooling g

Strany 31 - NTER key to confirm

29InRow RD 10 kW Air Cooled Operation and MaintenanceRespond to AlarmsWhen an alarm is triggered, the cooling unit alerts you through the display inte

Strany 32 - Display units

InRow RD 10 kW Air Cooled Operation and Maintenance30High Suction Pres(High Suction Pressure)Warning • Check the air filter and fans for obstructions•

Strany 33 - ENTER to

31InRow RD 10 kW Air Cooled Operation and MaintenanceSuction Pressure Sensor Failure Warning • Make sure the sensor is connected properly. • If the pr

Strany 35 - About the cooling unit

InRow RD 10 kW Air Cooled Operation and Maintenance32Network Management CardQuick ConfigurationThe cooling unit is shipped with a Network Management C

Strany 36 - Event Log

33InRow RD 10 kW Air Cooled Operation and MaintenanceAPC Device IP Configuration WizardYou can use the APC Device IP Configuration Wizard at a compute

Strany 37 - Respond to Alarms

InRow RD 10 kW Air Cooled Operation and Maintenance34BOOTP. For the Network Management Card to use a BOOTP server to configure its TCP/IP settings, it

Strany 38

35InRow RD 10 kW Air Cooled Operation and MaintenanceLocal access to the control consoleYou can use a computer connected to the serial port on the mai

Strany 39

InRow RD 10 kW Air Cooled Operation and Maintenance361. Use Ping with a size of 113 bytes to assign the IP address defined by the ARP command. For the

Strany 40 - Network Management Card

37InRow RD 10 kW Air Cooled Operation and MaintenanceAccess a Configured Network Management CardOverviewAfter the Network Management Card is running o

Strany 41 - .ini file utility

InRow RD 10 kW Air Cooled Operation and Maintenance38Telnet and SSHYou can access the control console through Telnet or Secure SHell (SSH), depending

Strany 42 - 04) is the length

39InRow RD 10 kW Air Cooled Operation and MaintenanceSimple Network Management Protocol (SNMP)SNMPv1 only. After you add the PowerNet® MIB to a standa

Strany 43

InRow RD 10 kW Air Cooled Operation and Maintenance40Recover From a Lost PasswordYou can use a local computer (a computer that connects to the Network

Strany 44 - TCP/IP from the Network menu

41InRow RD 10 kW Air Cooled Operation and MaintenanceMaintenanceMonthly Preventive MaintenancePhotocopy the following pages and use them during the ma

Strany 45 - Web interface

ContentsInRow RD 10 kW Air Cooled Operation and Maintenance iGeneral Information... 1Overview .

Strany 46 - Telnet and SSH

InRow RD 10 kW Air Cooled Operation and Maintenance42MechanicalElectrical Hazard: Turn off the cooling unit and disconnect all power sources. Perform

Strany 47

43InRow RD 10 kW Air Cooled Operation and MaintenanceQuarterly Preventive MaintenancePerform all the Monthly Preventive Maintenance items and the item

Strany 48 - Recover From a Lost Password

InRow RD 10 kW Air Cooled Operation and Maintenance44TroubleshootingProblem Possible Cause Corrective ActionControls erratic or inoperative• Inlet tem

Strany 49

45InRow RD 10 kW Air Cooled Operation and MaintenanceCooling unit does not shut down on command• Drive voltage • Verify that there is a drive voltage

Strany 52 - Troubleshooting

11/2009990-3212A-001APC Worldwide Customer SupportCustomer support for this or any other APC product is available at no charge in any of the following

Strany 53

ii InRow RD 10 kW Air Cooled Operation and MaintenanceContacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Strany 54

InRow RD 10 kW Air Cooled Operation and Maintenance iiiNetwork Management Card... 32Quick Configuration . . . .

Strany 56 - 11/2009990-3212A-001

1InRow RD 10 kW Air Cooled Operation and MaintenanceGeneral InformationOverviewNote the definitions for the icons here and be observant for them throu