®C—0 Hzhilled Water/Direct Expansion 50/6Technical DataAIR-COOLEDACRP100ACRP101ACRP102CHILLED WATERACRP500ACRP501ACRP502

Strany 2

InRow RP Technical Data Manual4Standard FeaturesInsulated CabinetThe frame is constructed of 1.5 mm (16 gauge) formed steel for maximum strength. Cabi

Strany 3 - Contents

5InRow RP Technical Data ManualDual Position Float Condensate ManagementThe pump is factory wired and piped internally to the condensate drain pan and

Strany 4

InRow RP Technical Data Manual6Optional FeaturesCable Water DetectorA leak detection cable is placed on the floor or subfloor around all possible leak

Strany 5

7InRow RP Technical Data ManualMicroprocessor ControllerMicroprocessor Controller The microprocessor controller is standard on each system. The contro

Strany 6

InRow RP Technical Data Manual8AlarmsThe microprocessor controller shall activate a visible and audible alarm in the following occurrences:• Cool Fai

Strany 7 - Overview

9InRow RP Technical Data ManualInRow RP ModelsHinged rear doorsCasters (all swiveling)Side panel lockDoor handle and lockRemovable side panelDis

Strany 8 - Environments

InRow RP Technical Data Manual10Chilled water interior components (front of unit)Electric heater (for reheat)Electrical panelFanSupply temperature

Strany 9 - Hot Aisle Containment System

11InRow RP Technical Data ManualChilled water interior components (back of unit)Chilled water coilRear doorsChilled water control actuatorAir filt

Strany 10 - Standard Features

InRow RP Technical Data Manual12Air-cooled interior components (front of unit)Electric heater (for reheat)Main circuit breakerCondensate drain pan

Strany 11

13InRow RP Technical Data ManualAir-cooled interior components (back of unit)Evaporator coilShutoff valves (top piping only)Condensate drain panAi

Strany 12 - Optional Features

American Power Conversion Legal DisclaimerThe information presented in this manual is not warranted by the American Power Conversion Corporation to be

Strany 13 - Microprocessor Controller

InRow RP Technical Data Manual14Chilled water and air-cooled user interface connectionsRack inlet temperature sensors 1, 2, 3A-Link INA-Link OUTNe

Strany 14 - Air-cooled Only Alarms

15InRow RP Technical Data ManualChilled water electrical panelNote: ACRP 501 shown. Transformers User interface connectors Main controller board R

Strany 15 - InRow RP Models

InRow RP Technical Data Manual16Air-cooled electrical panelNote: ACRP 101 shown. Transformers User interface connectors Main controller board Rela

Strany 16

17InRow RP Technical Data ManualPerformance SpecificationsChilled Water Performance Specifications 5.5°C (42°F) EWTTemperature dry bulb (DB), wet bulb

Strany 17

InRow RP Technical Data Manual18Chilled Water Performance Specifications 7.2°C (45°F) EWTTemperature dry bulb (DB), wet bulb (WB)°C (°F)CW Delta T°C (

Strany 18

19InRow RP Technical Data ManualChilled Water Performance Specifications 8.9°C (48°F) EWT (Temperature dry bulb (DB), wet bulb (WB)°C (°F)CW Delta T°C

Strany 19

InRow RP Technical Data Manual20Chilled Water Performance Specifications 10°C (50°F) EWTTemperature dry bulb (DB), wet bulb (WB)°C (°F)CW Delta T°C (°

Strany 20

21InRow RP Technical Data ManualChilled Water Performance Specifications 12.8°C (55°F) EWTTemperature dry bulb (DB), wet bulb (WB)°C (°F)CW Delta T°C

Strany 21 - Note: ACRP 501 shown

InRow RP Technical Data Manual22Chilled Water Performance Specifications 15.5°C (60°F) EWTTemperature dry bulb (DB), wet bulb (WB)°C (°F)CW Delta T°C

Strany 22 - Note: ACRP 101 shown

23InRow RP Technical Data ManualChilled Water Data - GeneralMODEL ACRP 500 SeriesMODULATING VALVESSize -3 Way Ball Valve - NPT mm (in) 25.4 (1)AIR SYS

Strany 23 - Performance Specifications

ContentsInRow RP Technical Data ManualiOverview ... 1Capacity . . . . . . . .

Strany 24 - ÷ 2.307 = PSIG

InRow RP Technical Data Manual24Glycol Correction FactorsAltitude Correction Factors for InRow ProductsAir-cooled Performance SpecificationsPerformanc

Strany 25

25InRow RP Technical Data ManualAir-cooled Data - GeneralMODEL ACRP 100 SeriesAIR SYSTEM - FAN (Standard Filter Installed)Air Volume - l/s (SCFM) 2265

Strany 26

InRow RP Technical Data Manual26Sound Performance DataChilled Water Tested Sound DataFan Speed%Airflow m3/s (SCFM)Sound Power dB at Frequency Hz re:

Strany 27

27InRow RP Technical Data ManualElectrical DataSKU Voltage MCA MOP LRA RLA FLA HzPower (kW)ACRP100 200 - 240 80.1 100 160* 50.0 N/A 50/60 19ACRP101 46

Strany 28

InRow RP Technical Data Manual28Dimensional DataInRow RP Assembled ModuleDimensions are shown in mm (in).na2465a

Strany 29 - Chilled Water Data - General

29InRow RP Technical Data ManualSX to VX Height AdapterSX to 48U SX Height AdapterDimensions are shown in mm (in).na2445ana2446a

Strany 30 - Glycol Correction Factors

InRow RP Technical Data Manual30Piping and Mechanical ConnectionsChilled water piping diagramFlex hose or copper Circuit setter (field-installed)Coppe

Strany 31 - Air-cooled Data - General

31InRow RP Technical Data ManualNote: Top or bottom entry can be chosen individually for each type of connection, i.e. power, condensate drain, humidi

Strany 32 - Sound Performance Data

InRow RP Technical Data Manual32Bottom chilled water piping access (bottom view, looking up)Dimensions are shown in mm (in).Humidifier supplyCondens

Strany 33 - Electrical Data

33InRow RP Technical Data ManualAir-cooled piping diagramNote: Shutoff valves shown nearest to the condensers are not supplied by APC.Note: Route pipi

Strany 34 - Dimensional Data

InRow RP Technical Data ManualiiOptional Features...6Cable Water Detector . . . . . . . . .

Strany 35 - SX to 48U SX Height Adapter

InRow RP Technical Data Manual34Air-cooled piping access (top)Dimensions are shown in mm (in). Refrigerant discharge line Refrigerant liquid line P

Strany 36 - Chilled water piping diagram

35InRow RP Technical Data ManualAir-cooled piping access (bottom view, looking up)Dimensions are shown in mm (in).Humidifier water supplyCondensate

Strany 37

InRow RP Technical Data Manual36Air-Cooled CondensersMechanical DataSKUAmbient TempSound Pressure (dbA) at 10 ft and 100% Fan SpeedSounds Pressure (db

Strany 38

37InRow RP Technical Data ManualACCD75201 and ACCD75204ACCD75202 and ACCD75205ACCD75203 and ACCD75206Dimensions are shown in mm (in). All co

Strany 39 - Air-cooled piping diagram

InRow RP Technical Data Manual38ACCD75207ACCD75208 and ACCD75209Dimensions are shown in mm (in). All condensers shown on this page have 16 m

Strany 40

39InRow RP Technical Data ManualGuide SpecificationsPART 1 — GENERAL1.01 SUMMARYA. The environmental control system shall be designed specifically for

Strany 41

InRow RP Technical Data Manual40PART 2 — PRODUCT2.01 STANDARD COMPONENTSA. CABINET CONSTRUCTION1. Exterior panels shall be 1.2 mm (18 gauge) steel. Fr

Strany 42 - Air-Cooled Condensers

41InRow RP Technical Data ManualD. MAIN DISCONNECT SWITCH1. Unit shall be provided with Thermal-Magnetic circuit breakers with interrupt capacity rati

Strany 43 - ACCD75203 and ACCD75206

InRow RP Technical Data Manual42s. Humidifier excessive output reductiont. Humidifier drain faultu. Humidifier cylinder fullv. Humidifier replace cyli

Strany 44 - Air-cooled Condenser Features

43InRow RP Technical Data Manual4. Logging: The microprocessor controller shall log and display all available events. Each alarm log shall contain tim

Strany 45 - Guide Specifications

InRow RP Technical Data ManualiiiDimensional Data...28InRow RP Assembled Module . . . . . . .

Strany 46

InRow RP Technical Data Manual44H. VARIABLE SPEED COMPRESSOR / VFD ASSEMBLY (AIR-COOLED ONLY)1. Compressor: The unit shall be configured with a variab

Strany 47 - 460-480V 60Hz 22

45InRow RP Technical Data ManualL. HUMIDIFIERHumidifier shall be able to modulate capacity. The humidifier shall be self-contained, steam-generating t

Strany 48

InRow RP Technical Data Manual46P. SELECTABLE TOP OR BOTTOM PIPING (AIR-COOLED ONLY)1. Pipe connections: The unit is equipped with field connection fr

Strany 49

47InRow RP Technical Data ManualGuidelines for InstallationThe InRow RP provides reliable, accurate temperature control of computer rooms, laboratorie

Strany 52

10/2008990-2469D-001*990-2469D-001*APC Worldwide Customer SupportCustomer support for this or any other APC product is available at no charge in any o

Strany 54

1InRow RP Technical Data ManualOverviewThe modular, row-based computer room cooling system offers efficient, predictable, and economical cooling for a

Strany 55

InRow RP Technical Data Manual2Scalable Solution for Critical EnvironmentsInRow AdvantagesThe row-based solution improves energy efficiency and coolin

Strany 56 - *990-2469D-001*

3InRow RP Technical Data ManualHot Aisle Containment System Modular ceiling tiles and doors can be used to enclose the hot aisle. This increases the d