APC ACCD75208 Servisní příručka

Procházejte online nebo si stáhněte Servisní příručka pro Komponenty chlazení počítače APC ACCD75208. APC Condenser 1 EC Fan Uživatelská příručka

  • Stažení
  • Přidat do mých příruček
  • Tisk

Shrnutí obsahu

Strany 1 - Technical Data

InRow® RPChilled Water/Direct Expansion — 50/60 HzTechnical DataAIR-COOLEDACRP100ACRP101ACRP102CHILLED WATERACRP500ACRP501ACRP502

Strany 2

InRow RP Technical Data Manual6Optional FeaturesCable Water DetectorA leak detection cable is placed on the floor or subfloor around all possible leak

Strany 3 - Contents

7InRow RP Technical Data ManualMicroprocessor ControllerMicroprocessor Controller The microprocessor controller is standard on each system. The contro

Strany 4

InRow RP Technical Data Manual8AlarmsThe microprocessor controller shall activate a visible and audible alarm in the following occurrences:• Cool Fai

Strany 5 - Overview

9InRow RP Technical Data ManualInRow RP ModelsHinged rear doorsCasters (all swiveling)Side panel lockDoor handle and lockRemovable side panelDis

Strany 6 - Environments

InRow RP Technical Data Manual10Chilled Water Interior Components (front of unit)Electric heater (for reheat)Electrical panelFanSupply temperature

Strany 7 - Hot Aisle Containment System

11InRow RP Technical Data ManualChilled Water Interior Components (back of unit)Chilled water coilRear doorsChilled water control actuatorAir filt

Strany 8 - Standard Features

InRow RP Technical Data Manual12Air-cooled Interior Components (front of unit)Electric heater (for reheat)Main circuit breakerCondensate drain pan

Strany 9

13InRow RP Technical Data ManualAir-cooled Interior Components (back of unit)Evaporator coilShutoff valves (top piping only)Condensate drain panAi

Strany 10 - Optional Features

InRow RP Technical Data Manual14Chilled Water and Air-cooled User Interface ConnectionsRack inlet temperature sensors 1, 2, 3A-Link INA-Link OUTNe

Strany 11 - Microprocessor Controller

15InRow RP Technical Data ManualChilled Water Electrical PanelNote: ACRP501 shown. Transformers User interface connectors Main controller board Re

Strany 12 - Air-cooled Only Alarms

American Power Conversion Legal DisclaimerThe information presented in this manual is not warranted by the American Power Conversion Corporation to be

Strany 13 - InRow RP Models

InRow RP Technical Data Manual16Air-cooled Electrical PanelNote: ACRP 101 shown. Transformers User interface connectors Main controller board Rela

Strany 14

17InRow RP Technical Data ManualPerformance SpecificationsChilled Water Performance Specifications 5.5°C (42°F) EWTTemperature dry bulb (DB), wet bulb

Strany 15

InRow RP Technical Data Manual18Chilled Water Performance Specifications 7.2°C (45°F) EWTTemperature dry bulb (DB), wet bulb (WB)°C (°F)CW Delta T°C (

Strany 16

19InRow RP Technical Data ManualChilled Water Performance Specifications 8.9°C (48°F) EWT (Temperature dry bulb (DB), wet bulb (WB)°C (°F)CW Delta T°C

Strany 17

InRow RP Technical Data Manual20Chilled Water Performance Specifications 10°C (50°F) EWTTemperature dry bulb (DB), wet bulb (WB)°C (°F)CW Delta T°C (°

Strany 18

21InRow RP Technical Data ManualChilled Water Performance Specifications 12.8°C (55°F) EWTTemperature dry bulb (DB), wet bulb (WB)°C (°F)CW Delta T°C

Strany 19 - Note: ACRP501 shown

InRow RP Technical Data Manual22Chilled Water Performance Specifications 15.5°C (60°F) EWTTemperature dry bulb (DB), wet bulb (WB)°C (°F)CW Delta T°C

Strany 20 - Air-cooled Electrical Panel

23InRow RP Technical Data ManualChilled Water Data - GeneralMODEL ACRP 500 SeriesMODULATING VALVESSize -3 Way Ball Valve - NPT mm (in) 25.4 (1)AIR SYS

Strany 21 - Performance Specifications

InRow RP Technical Data Manual24Glycol Correction FactorsAltitude Correction Factors for InRow ProductsAir-cooled Performance SpecificationsPerformanc

Strany 22

25InRow RP Technical Data ManualAir-cooled Data - GeneralNote: Reduce airflow and cooling capacity specifications by 7% for cooling units run at low i

Strany 23

ContentsInRow RP Technical Data ManualiOverview ... 1Capacity . . . . . . . .

Strany 24

InRow RP Technical Data Manual26Sound Performance DataElectrical DataChilled Water Tested Sound DataFan Speed% Airflow m3/s (SCFM)Sound Power dB at F

Strany 25

27InRow RP Technical Data ManualDimensional DataInRow RP Assembled ModuleDimensions are shown in mm (in).na2465a

Strany 26

InRow RP Technical Data Manual28SX to VX Height AdapterSX to 48U SX Height AdapterDimensions are shown in mm (in).na2445ana2446a

Strany 27 - Chilled Water Data - General

29InRow RP Technical Data ManualPiping and Mechanical ConnectionsChilled Water Piping DiagramFlex hose or copper Circuit setter (field-installed)Coppe

Strany 28 - Glycol Correction Factors

InRow RP Technical Data Manual30Top Chilled Water Piping Access (top view)Note: Top or bottom entry can be chosen individually for each type of connec

Strany 29 - Air-cooled Data - General

31InRow RP Technical Data ManualBottom Chilled Water Piping Access (bottom view, looking up)Dimensions are shown in mm (in).Water supply to chillerW

Strany 30 - Electrical Data

InRow RP Technical Data Manual32Air-cooled Piping DiagramNote: Shutoff valves shown nearest to the condensers are not supplied by APC.Note: Route pipi

Strany 31 - Dimensional Data

33InRow RP Technical Data ManualAir-cooled Piping Access (top)Dimensions are shown in mm (in). Refrigerant discharge line Refrigerant liquid line P

Strany 32 - SX to 48U SX Height Adapter

InRow RP Technical Data Manual34Air-cooled Piping Access (bottom view, looking up)Dimensions are shown in mm (in).Pressure relief valve access—27.80

Strany 33 - Chilled Water Piping Diagram

35InRow RP Technical Data ManualAir-Cooled CondensersMechanical DataSKUAmbient TempSound Pressure (dbA)*Sound Pressure (dbA) **Air Quantity Fan Unit C

Strany 34

InRow RP Technical Data ManualiiInRow RP Models ... 9Chilled Water Interior Components (front

Strany 35

InRow RP Technical Data Manual36ACCD75201 and ACCD75204ACCD75202 and ACCD75205ACCD75203 and ACCD75206Dimensions are shown in mm (in).Note: All condens

Strany 36 - Air-cooled Piping Diagram

37InRow RP Technical Data ManualACCD75207ACCD75208 and ACCD75209Dimensions are shown in mm (in). All condensers shown on this page have 16 m

Strany 37

InRow RP Technical Data Manual38Guide SpecificationsPART 1 — GENERAL1.01 SUMMARYA. The environmental control system shall be designed specifically for

Strany 38

39InRow RP Technical Data ManualB. VARIABLE SPEED FAN ASSEMBLY1. Variable Speed Fans: The unit is equipped with variable speed, electronically commuta

Strany 39 - Air-Cooled Condensers

InRow RP Technical Data Manual40k. Fan faultl. Fan run hours exceededm. Water detection faultn. Condensate pump faulto. Condensate run hours exceededp

Strany 40 - ACCD75203 and ACCD75206

41InRow RP Technical Data Manualba. Air flow decreased while compressor offbb. Suction pressure sensor failurebc. Discharge pressure sensor failurebd.

Strany 41 - Air-cooled Condenser Features

InRow RP Technical Data Manual42J. CONDENSATE PUMPFactory installed and wired condensate pump shall pump at 31.99 l/h (8.45 GPH) at 3.5 m (11.5 ft) of

Strany 42 - Guide Specifications

43InRow RP Technical Data ManualP. SELECTABLE TOP OR BOTTOM PIPING (AIR-COOLED ONLY)1. Pipe connections: The unit is equipped with field connection fr

Strany 43 - 460-480V 60Hz 22

InRow RP Technical Data Manual44Guidelines for InstallationThe InRow RP provides reliable, accurate temperature control of computer rooms, laboratorie

Strany 45

1InRow RP Technical Data ManualOverviewThe modular, row-based computer room cooling system offers efficient, predictable, and economical cooling for a

Strany 46

9/2009990-2469E-001APC Worldwide Customer SupportCustomer support for this or any other APC product is available at no charge in any of the following

Strany 47

InRow RP Technical Data Manual2Scalable Solution for Critical EnvironmentsInRow AdvantagesThe row-based solution improves energy efficiency and coolin

Strany 48 - Guidelines for Installation

3InRow RP Technical Data ManualHot Aisle Containment System Modular ceiling tiles and doors can be used to enclose the hot aisle. This increases the d

Strany 49

InRow RP Technical Data Manual4Standard FeaturesInsulated CabinetThe frame is constructed of 1.5 mm (16 gauge) formed steel for maximum strength. Cabi

Strany 50 - 9/2009990-2469E-001

5InRow RP Technical Data ManualDual Position Float Condensate ManagementThe pump is factory wired and piped internally to the condensate drain pan and